EA4 NTC 0x041 TmplMonrInitFlt
NTC Temporal Monitor Init Fault
Overview - NTC 0x040
FDD: ES005A
Description:
This diagnostic is responsible for detecting Temporal Monitor Initialization faults.
Diagnostic Overview:
The temporal Monitor initialization has a sequence of events. Faults at any one of these events are captured by the NTC 0x040. The sequence of events are monitored by a counter variable TmplMonrInitCntr.
Typical Fault Response:
- –F1 Failure 
 
 
Probable Sources (Most to Least Probable):
- •Temporal Monitor IC(A4412) fault. 
- •Temporal Monitor SPI fault. 
- •WD_Monitor pulse fault. 
- •POE fault. 
 
 
| Initialization | |
| Periodic | X | 
| Event | 
| Bit | Cause | 
| 0 | Fault Occured Between TmplMonrInitCntr = 10 ~ 11 | 
| 1 | Fault Occured Between TmplMonrInitCntr = 13(AND Gate Fault) | 
| 2 | Fault Occured Between TmplMonrInitCntr = 15 ~ 16 | 
| 3 | Fault Occured at TmplMonrInitCntr = 18 (POE Fault) | 
| 4 | Fault Occured at TmplMonrInitCntr = 19 (WD_STATE Fault) | 
| 5 | Fault Occured at TmplMonrInitCntr = 21 (Edge/Valid Write Fault) | 
| 6 | Fault Occured at TmplMonrInitCntr = 53 (POE + Non-WD Fault) | 
| 7 | Fault Occured at TmplMonrInitCntr = 53 (POE + WD Fault) | 
| Rev | Revision | 
| Initial Release | |